KYN28A-12 (GZS1) metal armored removable switch cabinet
KYN28A-12 (GZS1) metal armored removable switch cabinet is an indoor complete power distribution device for three-phase AC 50Hz, rated voltage 3.6~12KV single busbar and single busbar sectional system. It is suitable for indoor power supply systems in various power plants, substations, airports, docks, factories, mines, enterprises, hotels, high-rise financial buildings and civil buildings, etc., for the purpose of receiving and distributing electric energy and monitoring and protecting the power grid.
Application ScenariosPower Substations, Industrial Plants, Commercial Buildings, Data Centers
Details
Product Introduction
KYN28A-12 (GZS1) metal armored removable switch cabinet is an indoor complete power distribution device for three-phase AC 50Hz, rated voltage 3.6~12KV single busbar and single busbar sectional system. It is suitable for indoor power supply systems in various power plants, substations, airports, docks, factories, mines, enterprises, hotels, high-rise financial buildings and civil buildings. It is used to receive and distribute electric energy and monitor and protect the power grid. The switch cabinet hasprevent mis-dividing and closingCircuit breaker; Prevent opening and closing under loadIsolation switch;Prevent live hanging (closed)Ground wire(Ground switch); prevent the circuit breaker with a grounding wire (grounding switch) from closing; prevent the electrical five-proof entry into the live intervalfunction, it is a power distribution device with superior performance. SwitchThe main components in the cabinet are domestic VS1 vacuum circuit breakers, or 3AE of General Siemens, VD4 of ABB and HVX12 of Schneider.
The switch cabinet complies with the requirements of the national standard GB3906 and the Ministry of Electric Power standard DL/T404, and has passed the type test of the National High Voltage Electrical Equipment Quality Supervision and Inspection Center.
Model and meaning
KYN28A-12
K—Armored metal-enclosed switchgear
Y—Removable
N—Conditions of use: (indoor)
28—Design serial number
12—Rated voltage (kV)
Product Features
1. Successfully passed Multiple test demonstrations such as condensation, temperature rise, mechanical operation and mechanical life, insulation, short-circuit opening and closing, internal combustion arc, etc. fully meet the different needs of different users for switch equipment;
2. The grounding switch adopts a quick closing mechanism with short-circuit closing capability. A mechanical lock is installed on the connecting rod of the operating mechanism. When the grounding switch is in the closing state, it can prevent the circuit breaker handcart from being pushed into the circuit breaker or accidentally entering the live interval. The grounding switch can also be equipped with a locking electromagnet to achieve electrical interlocking between the grounding switch and non-cabinets;
3. The valve driving mechanism can be equipped with an electrical locking device to prevent exposure of live static contacts due to misoperation when the circuit breaker handcart is removed from the position, ensuring personal and equipment safety;
4. Prioritize the use of Xuji series microcomputer protection devices to achieve perfect coordination between the main circuit and the control circuit. Other types of protection devices can also be used to achieve intelligent operation of switching equipment;
5. Switching equipment can also be used The use of front-mounted current transformers makes equipment inspection and maintenance more convenient. The current transformers can be pulled out directly from the front, truly realizing installation against the wall and back-to-back, reducing the floor space; ensuring that handcarts of the same specification can be freely interchanged, and handcarts of different specifications cannot enter the working position.
Serial number
Name
Unit
Required value
1
Ambient air temperature
Maximum temperature
℃
+40
Minimum temperature
-25
Maximum daily temperature difference
K
25
Hottest monthly average temperature
℃
30
Maximum annual average temperature
20
2
Altitude
m
≤1000
3
Filth level
Level III
4
Humidity
Daily average relative humidity
℃
≤95
Monthly average relative humidity
≤90
5
Seismic resistance (horizontal velocity)
m/s²
0.2g
6
The amplitude of the common mode voltage induced on the auxiliary and control loops due to the switching operation in the main loop
kV
≤1.6
Quoted standards GB/T 11022 Shared technical requirements for high-voltage switchgear and control equipment standards
GB 1207 Electromagnetic voltage transformer
GB 1208 Current transformer
GB 1984 High-voltage AC circuit breaker
GB 1985 High voltage AC isolating switch and grounding switch
GB 3906 3.6kV~40.5kV AC metal-enclosed switchgear and control equipment
GB/T 5585 Copper, aluminum and their alloy busbars for electrical purposes
GB 6450 Dry-type power transformer
GB 11032 AC gapless metal oxide arrester
GB/T 12022 Industrial sulfur hexafluoride
GB 15166.2 High-voltage AC fuses Part 2: Current-limiting fuses
GB 50150 Electrical installation engineering, electrical equipment handover test standards
GB/T 4109 Insulating bushings with AC voltage higher than 1000V
SD 318 Technical conditions for high-voltage switchgear locking device
DL/T 402 Technical conditions for ordering high-voltage AC circuit breakers
DL/T 404 3.6kV~40.5kV AC metal-enclosed switchgear and control equipment
DL/T 486 High-voltage AC isolating switch and grounding switch
DL/T 593 Common technical requirements for high-voltage switchgear and control equipment standards
JB/T 10305 3.6kV~40.5kV Technical conditions for organic material pillar insulators in high-voltage equipment users
IEC 62271-100 High voltage AC circuit breaker
Technical parameters
Name
Unit
Parameters
Rated frequency
Hz
50
Rated voltage
kV
12
Rated insulation level
Rated short-duration power frequency
Withstand current (1min)
kV
42 (to the ground and meet)
48 (isolated fracture)
Rated lightning impulse withstand voltage
kV
75 (to the ground and meet)
85 (isolated fracture)
Main bus rated current
A
630, 1250, 1600, 2000, 2500, 3150, 4000
Branch bus rated current
A
630, 1250, 1600, 2000, 2500, 3150, 4000
Rated short-time withstand current (4S)
kA
16, 20, 25, 31.5, 40
Rated peak withstand current
40, 50, 63, 80, 100
Protection level
Shell IP4X, compartment IP2X
Ordering Instructions
In order to provide products and solutions with high quality and efficiency, you need to provide the following information when ordering:
Main circuit wiring diagram, arrangement diagram, floor plan
Secondary schematic diagram
The model, specification and quantity of the main electrical components in the switch cabinet
Cabinet size
Electrical equipment summary table and quantity of accessories
Special requirements and instructions for technical parameters and other differences and product standard parameters